HOW FAR CAN 8 gauge wire carry 40 amps?
The rule of thumb is to go up one size larger if you plan on running the recommended wire size over 100 feet. This means that if you are planning on running 8-gauage wire for a 40 amp breaker over 100 feet, you should go to 6-gauge wire.
14 AWG | 50 feet |
---|---|
12 AWG | 60 feet |
10 AWG | 64 feet |
8 AWG | 76 feet |
6 AWG | 94 feet |
For a maximum of 40 amps, you'll need a wire gauge of 8. Many electric cooking appliances require 40 amps such as electric cooktops.
8 Gauge Wire Amp Rating
#8 Gauge THHN Copper Stranded Wire is the most popular single conductor copper wire we carry and is RATED FOR 55 AMPS @ 90°C.
8 AWG may carry a maximum of 70 Amps in free air, or 50 Amps as part of a 3 conductor cable.
For 50 amps, you could use 4 AWG wire with 85A ampacity (a bit of overkill but it's OK), but you can never use 8 AWG wire with 50A ampacity (you will fry the circuit). In most cases, 6 AWG is an almost perfectly-sized wire for a 50 amp breaker.
What size of wire do you need to run 200 feet? 30ga works if you are carrying small signals, although having an “active terminator” becomes critical due to the capacitance effects on such a long wire.
Size and Type of Conduit | 14 AWG Wire | 8 AWG Wire |
---|---|---|
1/2-inch EMT | 12 | 3 |
3/4-inch EMT | 22 | 6 |
1-inch EMT | 35 | 9 |
1 1/2-inch EMT | 84 | 22 |
Thus, in order to keep voltage drop at the camera to less than 3 volts given a camera load of 2 AMPs and a 400 foot paired wire run, we need to use a wire gauge in the range of 10-13 AWG.
All Things Considered. Size 8 wire can handle anywhere between 40 and 55 amps and the aluminum versions can handle 40 to 45 amps. This type of wiring has a lot of applications both in commercial and residential buildings.
What is 8 AWG wire used for?
This wire is 8 AWG, good for 55 Amp when used in conduit with less than 3 conductors. This wire is rated for use in dry or wet locations, raceways, or conduit. It can be used outside exposed to the weather as well, though the insulation is not 100% UV-proof and installation in conduit is recommended. Sold by the foot!
Wire Number (Gauge) | A.W.G. or B&S (Inches) | A.W.G. Metric (MM) |
---|---|---|
6 | 0.162" | 4.115mm |
7 | 0.1443" | 3.665mm |
8 | 0.1285" | 3.264mm |
9 | 0.1144" | 2.906mm |

To run 50 amps at 150 feet, you can use No. 4 AWG. The larger the wire diameter is defined by the smaller numbers on a wire.
You will likely need 2 AWG but that's going to be less than 4 AWG Cu. Secondly, you may want to consider running a conduit vs. direct burial.
NM-B is primarily used in residential wiring as a branch circuit for switches, outlets and other loads. NM-B may run in air voids of masonry block or tile walls where locations are not damp.
Calculating With Voltage Drop Considered
On the off-chance that your panels are rated at 110V/120V, the right wire size for 50 amp sub panel should be bumped up to 2 AWG copper or 1/0 AWG aluminum for 200 ft. The sizes for 100 ft will be 4 AWG copper and 3 AWG aluminum.
That means the #8 AWG wire (with exactly 50A amperage) is the perfect wire size for 40 amp circuit. Example: Let's say you want to create a 40 amp 240 volt circuit. What size wire do you need? You need a wire that can handle at least 50 amps, and that's the #8 AWG wire.
500 Feet – a 120-volt, 20 amp circuit would require 1/0 AWG wire. A 240 volt, 30 amp circuit would require 3/3 AWG wire.
Despite the common sense conclusion, #14 AWG is never used for a 20 amp circuit. Instead, we use bigger #12 AWG wire (close to 20 amp sub panel) and #10 AWG wire (100 feet or more from 20 amp sub panel).
A 8-gauge wire
There is no rule when it comes to using larger wire sizes. However, many professionals are recommended to use only 8-gauge wires as it is the maximum wire size for 30 Amp circuit. If you look at the 30 Amp wire gauge chart, you will also see that a thicker wire has a lower number.
What size wire do I need to run 300 feet?
for 300 feet for 100 amp rated service I would use Aluminum direct burial 1/0-1/0-1/0-1/0, the forth can be as low as #4 for the ground (but also in conduit, even if in conduit must still be rated underground wire and required by code also) Also note the size wire the breaker can handle, cannot cut strands to make fit, ...
A basic rule of thumb is this. For up to 500 watts RMS, 8 gauge is sufficient. In the 500 – 1000 watt RMS range, you want to run 4 gauge. From 1000 – 1500 watts RMS you should be running 2 gauge.
A: Per the 2020 NEC, 8/2 NM-B Cable is rated for 40 Amps at 140F (60C).
Yes, if it's approved for the line voltage and temperature and if connectors (e.g. wire nuts) are sized to fit. A lower gauge number means heavier wire, able to carry more current safely, with lower voltage drop for the same length, so it should be quite safe if fused correctly for 10-gauge.
At 1000 feet and 100 amps, I'm getting 2/0 copper or 4/0 aluminum to keep the voltage drop under 10% and that's quite a bit of voltage drop. At 200A it goes off the charts. If you step up to 480V things come much more in line and depending on the transformer you may be able to adjust for some of the voltage drop.
Over size cables can in some instances cause problems. In so far as they can reduce the resistance/impedance to such an extent, that the Prospective Fault Current can be higher than the breaking capacity of equipment connected to the circuit. The chances of such being an issue in a domestic installation, are slim.
Ten-gauge wire can run for up to 128 feet under 30 amps. For typical household applications, a wire of this size can handle up to 30 amps, but it's best to keep this figure in mind before you start your wiring project. The longer you run your wire, the more likely the voltage will drop.
Accordingly, the term "number 8 wire" came to represent the ingenuity and resourcefulness of New Zealanders, and the phrase "a number 8 wire mentality" evolved to denote an ability to create or repair machinery using whatever scrap materials are available on hand.
14-gauge conductors: White. 12-gauge conductors: Yellow. 10-gauge conductors: Orange. 6- and 8-gauge wire: Black.
Cable Type | THHN/THWN-2 |
---|---|
Conductor Material | Bare Copper |
Stranded or Solid | Stranded |
Number of Strands | 19 |
O.D. (Inches) | 0.213 |
What happens if wire gauge is too big?
If a wire gauge is “too big” then it is a lot more expensive and is harder to bend, as well as more difficult to attach with wire nuts or to switches.
For 30 amp service 100 feet away you would need a wire that can handle at least 45 amps. Luckily, the #8 AWG wire has a 50A ampacity. You can use the #8 AWG wire for sub panel 50 feet, 100 feet, and even 150 feet away.
“Twelve-gauge wire is good for 20 amps, 10-gauge wire is good for 30 amps, 8-gauge is good for 40 amps, and 6-gauge is good for 55 amps,” and “The circuit breaker or fuse is always sized to protect the conductor [wire].”
150 Foot Run – A 120-volt circuit on a 20 amp breaker will require 6/2 AWG wire for 150 feet.
According to the NEC, any household cooking appliance rated at 12kW or less can be served by a 40A circuit. Yours is over this so bumping up to a 50A would be required.
80% NEC Rule
This means that if you are using an 8 wire gauge for 40 amp, you are only allowed to use a 32 amps maximum of continuous loads. It is only applicable to use more than 80% up to the maximum capacity of the breaker if the usage is application start-up and does not exceed the breaker's maximum capacity.
10 Gauge Wire Amps
Default 10 gauge wire Ampacity (the wire's ability to carry current) is 30 Amps @60°C/140°F, 35 Amps @75°C/167°F, or 40 Amps @90°C/194°F.