Can 8 gauge wire handle 60 amps?
RULES OF THUMB
“Twelve-gauge wire is good for 20 amps, 10-gauge wire is good for 30 amps, 8-gauge is good for 40 amps, and 6-gauge is good for 55 amps,” and “The circuit breaker or fuse is always sized to protect the conductor [wire].”
60 amp wire size is either 6 AWG or 4 AWG wire (AWG stands for American Wire Gauge; standard wire sizing is the US) for 220V voltage. An amateur will use a 6 AWG wire size for 60 amp 220V. A professional will always use 4 AWG wire size for 60 amp 220V.
8 AWG may carry a maximum of 70 Amps in free air, or 50 Amps as part of a 3 conductor cable.
8 Gauge Wire Amp Rating
#8 Gauge THHN Copper Stranded Wire is the most popular single conductor copper wire we carry and is RATED FOR 55 AMPS @ 90°C.
In most situations, when calculating wire Ampacity, one uses 75°C/167°F maximum wire surface temperature meaning that for the 60 Amps current one should use either AWG 4 wires (up to 50 feet) or AWG 3 wires (up to 150 feet).
4 AWG size for a 60 amp wire. This is the best size wire for 60 amps and 50 amps. However, with a 60 amp wire, you can go sometimes use a 6 gauge wire if it is only a short run. Use THHN or RHW type insulation.
For 60 amps #6 wire is the right size. Use RHW or THHN type insulation.
For a maximum of 50 amps, you'll need a wire gauge of 6. Fifty amp breakers are most often used to power many different appliances.
This wire is 8 AWG, good for 55 Amp when used in conduit with less than 3 conductors. This wire is rated for use in dry or wet locations, raceways, or conduit. It can be used outside exposed to the weather as well, though the insulation is not 100% UV-proof and installation in conduit is recommended. Sold by the foot!
What size wire do I need to run 50 amps 200 feet?
Calculating With Voltage Drop Considered
On the off-chance that your panels are rated at 110V/120V, the right wire size for 50 amp sub panel should be bumped up to 2 AWG copper or 1/0 AWG aluminum for 200 ft.
In short, the perfect wire size for most 30 amp services is the #8 AWG wire with 50A ampacity. This is the common size wire for 30 amps 240 volt service, 30 amp 220 volt service, and so on.

For 60 amps #6 wire is the right size. Use RHW or THHN type insulation. Wire of # 8 gauge is only good for 50 amps.
In most cases, 6 AWG is an almost perfectly-sized wire for a 50 amp breaker. In limited cases, you will probably have to use a larger 4 AWG wire. That's when you have a long circuit and are sending electrical current at some distance (100 feet or more).
In these cases, having the proper wire size for each circuit breaker is necessary to prevent future electrical problems and ensure your devices' safety. If you look at a 40 amp wire size chart, you can see that the recommended wire size is a minimum of 8 gauge.
This all depends on the type of appliance. However, most ranges require a 50 amp 240-volt circuit that is wired with a 6 gauge wire. A 4 gauge wire will be best if the current will be travelling longer distances.
"The use of a 50 amp plug on kilns with a 60 amp circuit is a widespread and long standing practice that has been approved by UL."
8-gauge copper will handle fifty amps, but it will get hot (75 degrees C).
Yes, you can - BUT, the 60 Amp feed has a maximum number of branch circuits that is LESS than the number of positions in a 100 Amp panel; and you need to keep the total Ampacity of all your branch circuits under the limit for the main panel.
yes the 60-amp would meet the minimum requirement. In addition, please keep in mind that you need at least #6 copper wire to feed the garage to handle the heat load. The house panel will need a 60-Amp breaker also.
What size wire do you need for 70 amps?
For 70 amp, the right wire is either a gauge 3 aluminum or a gauge 4 copper.
As you can see, the maximum number of amps a 6 gauge wire can handle is 60 amps. This is the 6 AWG copper wire at 90°C (194°F).
Upgrading from 60 to 100 amps costs $800–$1,500, replacing a 200-amp panel with a 300-amp panel costs $1,800–$3,500, and upgrading to 400 amps costs $2,000–$4,000.
Assuming your wiring run won't reach 100 feet, to the point that it begins to cause voltage drops, then you can consider the correct 80 amp THHN wire size as 3 AWG copper. Likewise, 1 AWG is the suitable aluminum wire size for 80 amps.
Your standard wire size chart will tell you that 6 AWG wire, which is rated for 55 amps, should be the wire size for 50 amp circuits. At 50 feet, that should be fine. You can consider that as the maximum limit for how far will 6 gauge wire carry 50 amps safely.